Measuring duct airflow
Airflow is cross-sectional area multiplied by mean velocity. A 400 × 250 mm opening has 0.1 m² of area. At 5 m/s, it carries 0.5 m³/s, or 500 L/s.
A single center reading may miss slower air near the walls. The readings option averages velocities only when you confirm that each represents an equal area. The equal-area round duct has the same area; it does not have the same pressure loss or noise performance.
The velocity check compares the mean velocity with a few common rule-of-thumb ranges for quiet, low-velocity systems. Your design standard, the equipment data and the noise target decide the real limit.