Estimate two-wire DC drop and power loss from a cable specification, measured loop resistance or supplied resistivity.
Cable resistance from
V
A
Assumed constant.
Cable run
Per conductor, from the cable datasheet.
More options
Ω
Total for lugs, fuses and terminals. Enter 0 if already included in a measured loop.
%
Your own design limit. This tool does not choose a code limit.
Voltage drop at 10 A
5V10.42%
Load sees 43 V of 48 V
0 V48 V
Reaches the load Lost in cable
Compare with a target
Power loss
50 W
Loop resistance
0.5 Ω
Loop length
100 m
Resistive DC estimate at constant current. It does not check ampacity, fuses or electrical code.
Job summary with every input and result
The current travels out and back
A 50 m one-way run has 100 m of conductor in a matching two-wire loop. At 5 Ω/km, the cable resistance is 0.5 Ω. With 10 A, that produces 5 V of drop and 50 W of resistive loss.
Add connection resistance when it is not already included in the measurement. A measured loop value already includes both directions, so it is used once. The geometric method uses your supplied resistivity, conductor area and reference condition.
This calculator estimates resistive DC loss at a constant current. It does not choose cable ampacity, protective devices or an allowable code limit. Equipment may draw a different current when delivered voltage changes.